Lutro PHPM-PA-120-WH | Phase-Adaptive Power Module White
Dimensions and Mounting
Mount in 2-gang U.S. wallbox, 3.5 in (89 mm) deep or 4 × 4 in (102 × 102 mm) junction box, 2.1 in (53 mm) deep.
For indoor use only.
This device generates heat; mount only where ambient temperature is 32 to 104 °F (0 to 40 °C).
Mount with arrows facing up to ensure adequate cooling.
Allow 4.5 in (114 mm) above and below faceplates when mounting several modules in a vertical layout.
Units may butt together when mounted in a horizontal layout.
Mount so line (mains) voltage wiring is at least 6 ft (1.8 m) from sound or electronic equipment and wiring.
Mount within 7° of true vertical.
Power
Control voltage: 120 V~ only
Load voltage: 120 V~ only
Capacity: Full 16 A 120 V~: 1920 W 120 – 277 V~: 1920 – 4432 W 220 – 240 V~: 3520 – 3840 W
Frequency: 50 / 60 Hz
Load (output) power: Phase independent of control device / control voltage
Sources / Load Types
Operates these sources with a smooth, continuous, Square Law dimming curve: – Incandescent (tungsten)– Halogen– Magnetic low-voltage transformer (iron core)– Electronic (solid-state) low-voltage transformer (must be manufacturer-approved for reverse-phase control dimming)– Neon / Cold cathode
Incandescent and electronic low-voltage sources may be controlled on the same circuit / control zone. Up to 30% of the capacity of the unit can be used for incandescent lighting.
Incandescent and magnetic low-voltage sources may be controlled on the same circuit / control zone. Up to 30% of the capacity of the unit can be used for incandescent lighting.
Electronic low-voltage and magnetic low-voltage sources may NOT be controlled on the same circuit / control zone.
PHPM-PA- and PHPM-WBX- models are not for use with non-dim loads. Use switching power module (PHPM-SW-DV-WH) for non-dim loads.
Minimum load on power module is 10 W.
Output must be directly connected to
Features:
Provides dimming control for 1 zone of a full 16 A lighting load.
May be used to dim incandescent, halogen, electronic low-voltage, magnetic low-voltage, neon / cold cathode.
Phase-adaptive technology automatically selects leadingedge or trailing-edge dimming for low-voltage transformers.
Up to 3 power modules may be controlled by a single dimmer (C5-BMJ- will control only 1 module).
Use PHPM-WBX- models for 3-wire fluorescent dimmer input and PHPM-PA- models for 2-wire input.
PHPM-WBX- models can be used in conjunction with BCI-0-10 for 0 – 10 V dimming applications.
Models available for control voltage of 120 V~ only or 220 – 277 V~.
Models available for load voltage of 120 V~ only or 120 – 277 V~.
Compatible with 220 / 240 V~, non-CE systems. Contact Lutron for specific system applications.
Not for use with non-dim loads.
Works with 120 V~ or 220 – 277 V~ versions of:
Lutron in-wall neutral wire dimmers; see approved list in the Dimmers and Switches Specification Guide (Lutron P/N 3671746) at www.lutron.com (see Lighting Load Interfaces section)
GRAFIK Eye QS control units *
LP, LCP, and GP dimming panels **
HomeWorks QS remote power panels **
HomeWorks QS in-line dimmer
HomeWorks QS DIN-rail power modules
EcoSystem interface C5-BMJ-XXX †
Energi Savr Node PRO LED+ phase-adaptive fixture controller
RadioRA 2 neutral wire dimmers; see approved list in the specification submittal (Lutron P/N 369225) at www.lutron.com
HomeWorks QS neutral wire dimmers; see approved list in the specification submittal (Lutron P/N 369305) at www.lutron.com
Caséta Wireless neutral wire dimmers; see approved list in the specification submittal (Lutron P/N 369987) at www.lutron.com
Vive PowPak phase select dimming modules;
Overview:
Provides dimming control for 1 zone of a full 16 A lighting load.
May be used to dim incandescent, halogen, electronic low-voltage, magnetic low-voltage, neon / cold cathode. Phase-adaptive technology automatically selects leadingedge or trailing-edge dimming for low-voltage transformers. Up to 3 power modules may be controlled by a single dimmer (C5-BMJ- will control only 1 module).